Notes
1. The above measurements were taken at a London Bank with five floors of
computer systems.
2. In all cases the 3rd harmonic neutral current was substantially reduced
even
when the phase currents are unbalanced.
3. The total voltage harmonic distortion was reduced from over 9% to less
than 3%.
4. The UPS 3rd harmonic neutral current has been reduced from 213A to 63A,
the complete site is running cooler, and the phase balance and power factor
have been improved.