A CASE STUDY

 

Table 1 Typical multi HRT site measurements.

 

HRT

Currents Before HRT’s Installed

Currents After HRT’s Installed

Position

Red

Phase

Yellow

Phase

Blue

Phase

Neutral

Red

Phase

Yellow

Phase

Blue

Phase

Neutral

Main Riser 1 8.8A 23A 5.7A 23A 6.1A 21.5A 9.4A 18A
Main Riser 2 18A 17A 5.9A 20A 7.7A 10A 10A 13A
Main Riser 3 22A 35A 51A 46A 29A 32A 40A 11A
Distribution

Unit 1

31A 33A 12A 45A 20A 29A 20A 17A
Distribution

Unit 2

27A 29A 38A 43A 10A 22A 30A 24A
Distribution

Unit 3

17A 14A 17A 16A 14A 15A 18A 9.5A
Distribution

Unit 4

19A 1A 1A 19A 14A 7.5A 7A 8.5A
Main UPS 257A 185A 120A 213A 216A 172A 144A 63A

Notes

1. The above measurements were taken at a London Bank with five floors of

computer systems.

2. In all cases the 3rd harmonic neutral current was substantially reduced even

when the phase currents are unbalanced.

3. The total voltage harmonic distortion was reduced from over 9% to less

than 3%.

4. The UPS 3rd harmonic neutral current has been reduced from 213A to 63A,

the complete site is running cooler, and the phase balance and power factor

have been improved.

hrtexamples.jpg (326269 bytes)