3/2 PHASE TRANSFORMATION upto 350KVA

There are 2 main reasons for the need to transform from three phases to two phases,

  1. To give a supply to an existing two phase system from a three phase supply.
  2. To supply two phase furnace transformers from a three phase source.

TEC incorporates a special three phase core design which has two windings, the main and teaser, the centre limb is 41% larger in section and left unwound.

The three phase side is connected in a Tee formation, with the main winding wound for the full line volts and centre tapped, this winding is also interleaved so that any magnetic effect of a current entering at the centre point is cancelled out. The teaser winding is wound for 87% of the line volts with one end connected to the centre point of the main winding.

Each secondary is a simple single phase winding with the volts and amps no different from what would be expected in an ordinary single phase transformer.

wdia.jpg (32039 bytes)

ET = 0.87 Ep

Ip = 0.58 Qs/Ep

Is = Qs/2Es

Qs = KVA rating of 2 phase load.

RATING MAIN TEASER
Pri 0.58 Qs 0.5 Qs
Sec 0.5 Qs 0.5 Qs