Transformers manufactured by TEC for use in initial high inrush v.a. such as contactor or relay circuits, are designed with open circuit voltage 5% maximum above specified value.

The table below shows the maximum peak initial loads permissible for limited volt drop below the specified voltage. The continuous v.a. selected is that which will take final and/or initial v.a. whichever is the greater.

Continuous

VA

NL-FL

Voltage Drop

at rated VA

Peak

5%

(initial) VA

7.5%

Max value

10%

at UPF for

15%

50 9.6% 50 60 75 100
100 6.8% 107 140 180 250
150 6.5% 165 210 275 400
250 4.9% 400 525 700 950
350 4.8% 500 700 875 1200
400 3.9% 750 975 1250 1750
500 3.7% 1000 1300 1600 2100
600 3.15% 1300 1750 2200 3000
750 2.8% 1800 2400 3100 4250
1000 2.7% 2600 3500 4250 5750
1500 2.8% 3700 5000 6300 8600
2000 2.35% 6000 8000 10000 14000
2500 2.1% 8000 11000 14000 20000
3000 2.05% 10000 13500 17000 24000
3500 1.9% 12000 16000 20000 28000
4000 2.0% 13500 17500 22000 31000
4500 1.8% 16000 22000 27500 38000
5000 1.5% 21000 28500 36000 50000